273
FX3G/FX3U/FX3GC/FX3UC Series
Programming Manual - Basic & Applied Instruction Edition
10 Arithmetic and Logical Operation (
+
,
,
×
,
÷
) – FNC 20 to FNC 29
10.4 FNC 23 – DIV / Division
1
Introduction
2
Overview
3
Instruction
List
4
Devices
in Detail
5
Specified the
Device &
Constant
6
Before
Programming
7
Basic
Instruction
8
FNC00-FNC09
Program Flow
9
FNC10-FNC19
Move & Compare
10
FNC20-FNC29
Arith. & Logic
Operation
2. 32-bit operation (DDIV and DDIVP)
[ +1, ] indicates the dividend, [ +1, ] indicates the divisor, the quotient is transferred to
[ +1, ]), and the remainder is transferred to [ +3, +2].
Four devices in total starting from are occupied to store the operation result (quotient and remainder). Make
sure that these four devices are not used for another control.
The most significant bit of each data indicates the sign (positive: 0 or negative: 1), and data is divided algebraically.
5500 ÷ (540) = 10 (quotient) ... 100 (remainder)
When a constant (K) is specified in [ +1, ] or [ +1, ], it is automatically converted into binary
format.
Related devices
1. Relationship between flag operation and numeric value
*1. Available in all FX3G/FX
3GC
PLCs and FX3U/FX
3UC
PLCs Ver. 2.30 or later.
Cautions
1. Operation result
The most significant bit of the quotient and remainder indicates the sign (positive: 0, negative: 1) respectively.
The quotient is negative when either the dividend or divisor is negative.
The remainder is negative when the dividend is negative.
2. Device specified as
The remainder is not obtained when a bit device is specified with digit specification.
In a 32-bit operation (by DDIV or DDIVP), Z cannot be specified as .
Error
When the divisor is "0", an operation error is caused and the instruction is not executed.
A operation error results when the operation result is over 32,767 (16-bit operation) or 2,147,483,647 (32-bit
operation). (Turns the carry flag ON.)
Device Name Description
M8304
*1
Zero
ON : When the operation result is 0.
OFF : When the operation result is a number other than 0.
M8306
*1
Carry
ON : Carry flag operates when the operation result is over 32,767 (16-bit operation) or
2,147,483,647 (32-bit operation).
OFF : When the operation result is less than 32,767 (16-bit operation) or 2,147,483,647
(32-bit operation).
S
1
S
1
S
2
S
2
D
D
D
D
Quotient Remainder
BIN BIN
[ +1, ] ... [ +3, +2]
32 bits 32 bits
Dividend Divisor
BIN BIN
[ +1, ]
÷
[ +1, ]
32 bits 32 bits
Command
input
FNC 23
DDIV
D
D
D
D
D
S
1
S
2
S
1
S
2
S
1
S
2
D
S
1
S
1
S
2
S
2
D
D
S
2

Table of Contents

Other manuals for Mitsubishi FX3G Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX3G Series and is the answer not in the manual?

Mitsubishi FX3G Series Specifications

General IconGeneral
ModelFX3G Series
Power SupplyAC 100-240V or DC 24V
Program Capacity32, 000 steps
Execution Speed0.21 µs/basic instruction
Communication OptionsRS-422, USB, Ethernet
Expansion ModulesAnalog, digital, communication
Programming LanguageLadder Logic, Instruction List
Built-in FunctionsHigh-speed counters, pulse output
Analog I/OAvailable via expansion modules

Related product manuals