924
FX3G/FX3U/FX3GC/FX3UC Series
Programming Manual - Basic & Applied Instruction Edition
B Instruction Execution Time
B-6 Execution Time on Combination of Applicable Devices and Indexing
Appendix B-6 Execution Time on Combination of Applicable Devices and
Indexing
In examples shown below for basic instructions, the MOV instruction and data comparison instructions, the instruction
execution time varies depending on the combination of target devices and absence/presence of indexing.
The combinations of target devices marked with "*1" and "*2" are handled as exceptions because high-speed
processing is adopted in the technique.
Appendix B-6-1 Basic instruction (LD/LDI/AND/ANI/OR/ORI) execution time
•FX3U/FX3UC PLCs
•FX3G/FX3GC PLCs do not support indexing of bit devices and contact instructions with bit specification of word
devices in basic instructions.
Appendix B-6-2 Applied instruction execution time
1. MOV (FNC 12) instruction execution time
•FX3U/FX3UC PLCs
- MOV instruction (16-bit operation)
*1. These combinations are handled as exceptions because high-speed processing is adopted in the technique.
*2. When the instruction is executed for a BFM in a special function block/unit for FX3U/FX3UC Series.
- DMOV instruction (32-bit instruction)
*1. These combinations are handled as exceptions because high-speed processing is adopted in the technique.
*2. When the instruction is executed for a BFM in a special function block/unit for FX3U/FX3UC Series.
Specified device type Condition Instruction execution time (µs)
Bit device
Without indexing 0.065
With indexing 11.9
Word device Bit specification 8.8
Command
contact
S (source)
D (destination)
Without indexing (µs) With indexing (µs)
KnY,KnM,KnS T,C,D R
U\G
*2
KnY,KnM,KnS T,C,D R
U\G
*2
ON
KnX,KnY,KnM,KnS 15.5 12.1 13.8 212.9 18.6 16.6 16.9 214.7
T,C,D 12.1
0.64
*1
10.4 209.7 16.6 14.5 14.8 212.8
R 13.8 10.4 12.1 211.3 16.9 14.8 15.1 213.1
U\G
*2
131.8 128.5 130.2 377.9 133.1 129.9 131.5 379.4
K,H 12.5
0.64
*1
10.8 210.1 15.4 13.3 13.6 211.6
OFF
KnX,KnY,KnM,KnS
0.325
T,C,D
0.32
*1
R
U\G
*2
K,H
0.32
*1
Command
contact
S (source)
D (destination)
Without indexing (µs) With indexing (µs)
KnY,KnM,KnS T,C,D R
U\G
*2
KnY,KnM,KnS T,C,D R
U\G
*2
ON
KnX,KnY,KnM,KnS 15.5 12.4 13.8 311.1 18.7 17.0 17.1 313.0
T,C,D 12.4
1.48
*1
10.7 307.4 17.0 15.2 15.3 310.5
R 13.8 10.7 12.2 308.9 17.1 15.3 15.4 310.6
U\G
*2
199.8 195.9 197.4 542.6 201.2 197.3 198.8 544.0
K,H 13.0
1.48
*1
11.4 308.0 16.2 14.4 14.5 309.7
OFF
KnX,KnY,KnM,KnS
0.585
T,C,D
1.48
*1
R
U\G
*2
K,H
1.48
*1

Table of Contents

Other manuals for Mitsubishi FX3G Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX3G Series and is the answer not in the manual?

Mitsubishi FX3G Series Specifications

General IconGeneral
ModelFX3G Series
Power SupplyAC 100-240V or DC 24V
Program Capacity32, 000 steps
Execution Speed0.21 µs/basic instruction
Communication OptionsRS-422, USB, Ethernet
Expansion ModulesAnalog, digital, communication
Programming LanguageLadder Logic, Instruction List
Built-in FunctionsHigh-speed counters, pulse output
Analog I/OAvailable via expansion modules

Related product manuals