15 External FX I/O Device – FNC 70 to FNC 79
15.10 FNC 79 – TO / Write To A Special Function Block
15.10 FNC 79 – TO / Write To A Special Function Block
Outline
This instruction writes data from a PLC to buffer memories (BFM) in a special function unit/block.
When a large capacity of data is written to buffer memories (BFM) by this instruction, a watchdog timer error may
occur. When splitting the data to be written does not affect the control, use WBFM (FNC279) instruction.
For WBFM (FNC279) instruction, refer to Section 31.2.
1. Instruction format
2. Set data
3. Applicable devices
Explanation of function and operation
1. 16-bit operation (TO and TOP)
For the common items between FROM instruction and TO instruction, refer to Subsection 15.9.1.
PLC (word device) Special extension unit/block (BFM)
"n"-point 16-bit data starting from inside a PLC are transferred (written) to "n"-point buffer memories starting
from the buffer memory (BFM) # m2 inside a special function unit/block No. m1.
Operand Type Description Data Type
m1
Unit number of a special extension unit/block
(K0 to K7 from the right side of the main unit)
16- or 32-bit binary
m2 Transfer destination buffer memory (BFM) number 16- or 32-bit binary
Device number storing the transfer source data 16- or 32-bit binary
n Number of transfer points 16- or 32-bit binary
Oper-
and
Type
Bit Devices Word Devices Others
System User Digit Specification System User
Special
Unit
Index
Con-
stant
Real
Number
Charac-
ter String
Pointer
XYMTCSD
.b KnX KnY KnM KnS T C D R
U\G
V Z Modify K H E "
"P
m1 33 33
m2 33 33
3333333 333
n 33 33
P
FNC 79
TO
D
DTO
DTOP
Mnemonic Operation Condition
32-bit Instruction
17 steps
Continuous
Operation
Pulse (Single)
Operation
16-bit Instruction
9 steps
Mnemonic Operation Condition
Continuous
Operation
Pulse (Single)
Operation
TO
TOP
S
S
S
Command
input
FNC 79
TO
m1 m2 nS
Unit No.
m1 = 0 to 7
Transfer destination (Special
extension unit/block) BFM #
m2 = 0 to 32766
Transfer source (PLC)
Number of transfer points
n = 1 to 32767

Table of Contents

Other manuals for Mitsubishi FX3G Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX3G Series and is the answer not in the manual?

Mitsubishi FX3G Series Specifications

General IconGeneral
ModelFX3G Series
Power SupplyAC 100-240V or DC 24V
Program Capacity32, 000 steps
Execution Speed0.21 µs/basic instruction
Communication OptionsRS-422, USB, Ethernet
Expansion ModulesAnalog, digital, communication
Programming LanguageLadder Logic, Instruction List
Built-in FunctionsHigh-speed counters, pulse output
Analog I/OAvailable via expansion modules

Related product manuals