32
FX3G/FX3U/FX3GC/FX3UC Series
Programming Manual - Basic & Applied Instruction Edition
2 Overview (Sequence Program)
2.5 Introduction of Devices Constructing PLC
8. Index registers (V)(Z)
Refer to Section 4.11.
Among registers, there are index type registers V
and Z used for modification.
A data register V or Z is added to another device as
follows:
[In the case of "V0, Z0 = 5"]
D100V0 = D105, C20Z0 = C25 Device number +
V or Z value
Data registers and index registers are used for
indirectly specifying the set value of timers and
counters, or used in applied instructions.
9. Pointers (P)(I)
Refer to Section 4.12.
Pointers are classified into branch pointers and
interrupt pointers.
A branch pointer (P) specifies the jump
destination of the conditional jump CJ (FNC 00) or
the call subroutine CALL (FNC 01) instruction.
An interrupt pointer (I) specifies the routine of an
input interrupt, timer interrupt or counter interrupt.
10.Constants (K)(H)(E)
Refer to Chapter 5.
Constant numerical values used in the PLC, "K"
indicates a decimal integer value, "H" indicates a
hexadecimal value, and "E" indicates a real number
(floating point data).
Constants are used as set values or present values
of timers and counters, or operands for applied
instructions.

Table of Contents

Other manuals for Mitsubishi FX3G Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX3G Series and is the answer not in the manual?

Mitsubishi FX3G Series Specifications

General IconGeneral
ModelFX3G Series
Power SupplyAC 100-240V or DC 24V
Program Capacity32, 000 steps
Execution Speed0.21 µs/basic instruction
Communication OptionsRS-422, USB, Ethernet
Expansion ModulesAnalog, digital, communication
Programming LanguageLadder Logic, Instruction List
Built-in FunctionsHigh-speed counters, pulse output
Analog I/OAvailable via expansion modules