826
FX3G/FX3U/FX3GC/FX3UC Series
Programming Manual - Basic & Applied Instruction Edition
37 Operation of Special Devices (M8000 -, D8000 -)
37.1 Special Device List (M8000 -, D8000 -)
Flags
[M]8300 to [M]8303 Not used –––
[M]8304 Zero
ON when the multiplication and division
calculated result is 0
3 3
3
*1
3
*1
–––
[M]8305 Not used
–––
[M]8306 Carry
ON when the division calculated result
overflows
3 3
3
*1
3
*1
–––
[M]8307 to [M]8311 Not used
–––
Unconnected I/O Designation Error (Refer to Chapter 38 for details.) and flag
[M]8312
*2
Real time clock data lost error
3 3 –––
[M]8313 to [M]8315 Not used –––
[M]8316
*3
Unconnected I/O designation error
3 3
D8316
D8317
–––
[M]8317 Not used
–––
[M]8318
BFM initialization failure
ON when a FROM/TO error has occurred in a
special function block/unit as specified in the
BFM initialization function at changing PLC
from STOP to RUN.
When M8318 turns ON, the unit number in
which the error has occurred is stored in
D8318, and the BFM number is stored in
D8319.
3
3
*4
D8318
D8319
–––
[M]8319 to [M]8321 Not used
–––
[M]8322
FX
3UC-32MT-LT/FX3UC-32MT-LT-2 model
indicator
1:FX3UC-32MT-LT-2
0:FX3UC-32MT-LT
3
*5
–––
[M]8323 CC-Link/LT configuration required
3
*5
–––
[M]8324 CC-Link/LT configuration completed
3
*5
–––
[M]8325 to [M]8327 Not used
–––
[M]8328 Instruction non-execution
3
3
*4
–––
[M]8329 Instruction execution abnormal end
3 3 3 3 –––
*1. Available in Ver. 2.30 or later.
*2. M8312 is EEPROM backed up against power failure, and is automatically cleared when it is cleared or when
the clock data is set again. For details on backup against power failure, refer to Section 2.6.
*3. If the I/O device numbers are unavailable, M8316 turns ON when its directly designated to device numbers
including LD, AND, OR, and OUT instructions or indirectly designated by index.
*4. Available in Ver. 2.20 or later.
*5. Only the FX
3UC-32MT-LT-2 is applicable.
Number and name Operation and function
Applicable model
FX
3G
FX
3GC FX3U
FX
3UC
Correspond-
ing special
device
FX
1S
FX
1N
FX
2N
FX
1NC
FX
2NC

Table of Contents

Other manuals for Mitsubishi FX3G Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX3G Series and is the answer not in the manual?

Mitsubishi FX3G Series Specifications

General IconGeneral
ModelFX3G Series
Power SupplyAC 100-240V or DC 24V
Program Capacity32, 000 steps
Execution Speed0.21 µs/basic instruction
Communication OptionsRS-422, USB, Ethernet
Expansion ModulesAnalog, digital, communication
Programming LanguageLadder Logic, Instruction List
Built-in FunctionsHigh-speed counters, pulse output
Analog I/OAvailable via expansion modules