PLC User's Manual - Analog Control Edition
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)
2. Specifications
This chapter describes the general, power supply, and performance specifications for the 4AD.
2.1 Generic Specifications
*1. The direct mounting method cannot be used with FX3UC-4AD.
*2.
→ For a detailed description of grounding, refer to Section 3.5.
*3. If the pressure is higher than the atmospheric pressure, do not use the 4AD; 4AD may malfunction.
Item Specifications
Ambient
temperature
0 to 55°C (32 to 131°F) when operating
-25 to 75°C (-13 to 167°F) when stored
Relative
humidity
5 to 95%RH (no condensation) when operating
Vibration
resistance
Frequency
(Hz)
Acceleration
(m/s
2
)
Half amplitude
(mm)
10 times of testing in
each direction (X-, Y-,
and Z-axis directions)
(Total: 80 min, each)
DIN Rail Mounting
10 - 57 - 0.035
57 - 150 4.9 -
Direct Mounting
*1
10 - 57 - 0.075
57 - 150 9.8 -
Shock
resistance
147 m/s
2
Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z
Noise
resistance
Using noise simulator of:
Noise voltage: 1,000Vp-p / Noise width: 1µs / Rise: 1ns / Cycle: 30 to 100Hz
Dielectric
withstand
voltage
500 V AC, for 1 min
Between all terminals and ground terminal
Insulation
resistance
5MΩ or more using 500V DC
insulation resistance meter
Grounding
Class D grounding (grounding resistance: 100 Ω or less)
<Common grounding with a heavy electrical system is not allowed.>
*2
Working
atmosphere
Free from corrosive or flammable gas and excessive conductive dust
Working
altitude
< 2000m
*3
PLC
Other
equipment
PLC
Other
equipment
PLC
Other
equipment
Shared grounding
Good condition
Common grounding
Not allowed
Independent grounding
Best condition