7. APPLICATION INSTRUCTIONS
7 48
MELSEC-A
ENCO
X00C
0
P K
ENCO M10 D8 3
CIRCUIT END
Coding
0 LD X00C
1 ENCOP M10 D8 K3
10 END
When 8 is specified as effective bits,
256 points are occupied.
When 3 is specified as effective bits,
8 points are occupied.
Device D8
Encode result
Which point, counting from M10, is on is stored in BIN.