7. APPLICATION INSTRUCTIONS
7 80
MELSEC-A
(9) If the TO(P)/DTO(P) instructions are executed to a remote terminal module
which is communicating with other module, execution of the instructions is again
performed to the same remote terminal module immediately after the
processing being executed.
Execution Conditions
Operation Errors In the following cases, operation error occurs and the error flag turns on.
When the station number specified at "n1" is not of a remote terminal.
When "n3" points which start with the device specified at (S) exceed the specified
device range.
When the device specified at (D1) is not a usable device.
When the communication request registration areas are full.
Program Examples TO , PRC
A program which writes constant K100 to address 3 of buffer memory of the AD61C
(head station number 1) when X0 is turned ON.
Device specified at (D2)
(Communication complete flag)
OFF
ON
Executed every
completion of
communication
Executed every
completion of
communication
Executed only once
Executed only once
P
Read command
Device specified at (D2)
(Communication complete flag)
K K K K
TO 1 3 100 1
PRC M0 Y000
0
X000
……... M0 turns ON when communication
processing is completed.
Coding
0 LD X000
1 TO K1 K3 K100 K1
10 PRC M0 Y000
17 END

Table of Contents

Other manuals for Mitsubishi MELSEC-A series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC-A series and is the answer not in the manual?

Mitsubishi MELSEC-A series Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC-A series
CategoryController
LanguageEnglish

Related product manuals