EasyManua.ls Logo

Mitsubishi MELSEC-A series - Page 419

Mitsubishi MELSEC-A series
508 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
APP - 14
APPENDICES
Table 1.2 Link Special Relay List (Continue)
Number Name Description Details
M9232
Local station
operating status
OFF:RUN or STEP RUN mode
ON: STOP or PAUSE mode
Depends on whether or not a local station is in STOP or
PAUSE mode.
M9233
Local station error
detect
OFF:No error
ON: Error detected
Depends on whether or not a local station has detected an
error in another station.
M9235
Local or remote I/O
station parameter
error detect
OFF:No error
ON: Error detected
Depends on whether or not a local or a remote I/O station
has detected any link parameter error in the master station.
M9236
Local or remote I/O
station initial
communicating status
OFF:Noncommunicating
ON: Communicating
Depends on whether or not a local or a remote I/O station is
communicating initial data (such as parameters) with the
master station.
M9237
Local or remote I/O
station error
OFF:Normal
ON: Error
Depends on the error condition of a local or remote I/O
station.
M9238
Local or remote I/O
station forward/
reverse loop error
OFF:Normal
ON: Error
Depends on the error condition of the forward and reverse
loop lines of a local or a remote I/O station.