MELSEC-A
Table 2.1 Instruction Processing Time of Small Size, Compact CPUs (Continue)
Processing Time (µs)
A2AS
(S1)
A2USH-S1
A2USH
board
A2C A52G A0J2H A1FX
Instruction Condition (Device)
R R R R R D R
X 0.20 0.09 1.3 1.0 1.3 2.3 0.25
LD, LDI,
AND, ANI,
OR, ORI
Y, M, L, B, F, T, C 0.20 0.09 1.3 1.0 1.3 1.0 0.25
ANB
ORB
 0.20 0.09 1.3 1.0 1.3 2.3 0.25
Unchanged
(OFF OFF, ON ON)
0.40 0.18 1.3 1.0 1.3 2.3 0.25
Y
Changed (OF F ON, ON OFF) 0.40 0.18 1.3 1.0 1.3 2.3 0.25
Unchanged
(OFF OFF, ON ON)
0.40 0.18 1.3 1.0 1.3 1.3 0.25
L, S, B
M (other than
special M)
Changed (OFF ON, ON OFF) 0.40 0.18 1.3 1.0 1.3 1.3 0.25
Special M 0.80 0.37 46 37 46 46 7.2
Unexecuted 2.8 1.28 76 61 76 76 12.3
26.34
F
Executed 99.0
60.90 *
829 663 829 829 52.2
Instruction execution time 0.40 0.18 1.3 1.0 1.3 1.3 0.25
Unexecuted 0.23 0.09 0 0 0 0 0
After time out 4.5 2.05 14 11 14 14 20.0
K 7.7 3.50 30 24 30 30 22.0
T
Processing
time at the
execution
of END
instruction
Exe-
cuted
Added
D 8.3 3.77 37 30 37 37 24.0
Instruction execution time 0.40 0.18 1.3 1.0 1.3 1.3 0.25
Unexecuted 0.27 0.12 0 0 0 0 0
Uncounted 0.27 0.12 0 0 0 0 0
After count out 0.27 0.12 0 0 0 0 0
K 4.2 1.91 31 25 31 31 12.0
OUT
C
Processing
time at the
execution
of END
instruction
Exe-
ciuted
Counted
D 4.8 2.18 37 30 37 37 15.2
Unexecuted 0.40 0.17 1.3 1.0 1.3 2.3 0.25
Unchanged (ON ON) 0.40 0.17 1.3 1.0 1.3 2.3 0.25
Y
Executed
Changed (OFF ON) 0.40 0.17 1.3 1.0 1.3 2.3 0.25
Unexecuted 0.40 0.17 1.3 1.0 1.3 1.3 0.25
Unchanged (ON ON) 0.40 0.17 1.3 1.0 1.3 1.3 0.25
M, L, S, B
Executed
Changed (OFF ON) 0.40 0.17 1.3 1.0 1.3 1.3 0.25
Unexecuted 0.80 0.36 3.0 3.0 3.0 3.0 1.0
Special M
B
Executed 0.80 0.36 40 32 40 40 6.2
Unexecuted 2.0 0.91 3.8 3.0 3.8 3.8 1.0
26.63
SET
F
Executed 99
61.17 *
638 638 638 638 46.1
R: Refresh mode, D: Direct mode
* Value for A2USH board

Table of Contents

Other manuals for Mitsubishi MELSEC-A series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC-A series and is the answer not in the manual?

Mitsubishi MELSEC-A series Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC-A series
CategoryController
LanguageEnglish

Related product manuals