Page #1128 background image
App-120
(2) Table of the time to be added when file register is used
(a) When using L02CPU, L26CPU-BT.
(3) Table of the time to be added when F/T(ST)/C device is used in OUT/SET/RST instruction
(a) When using L02CPU, L26CPU-BT.
Device name data
Device Specification
Location
Processing Time (µs)
L02CPU L26CPU-BT
File register (R)
When standard
RAM is used
Bit
Source
0.100 0.048
Destination
0.220 0.038
Word
Source
0.100 0.048
Destination
0.100 0.038
Double word
Source
0.200 0.095
Destination
0.200 0.086
File register (ZR),
Extended data register (D),
Extended link register (W)
When standard
RAM is used
Bit
Source
0.140 0.057
Destination
0.280 0.048
Word
Source
0.140 0.057
Destination
0.140 0.048
Double word
Source
0.240 0.105
Destination
0.240 0.095
Instruction name Device name Condition
Processing Time (µs)
L02CPU L26CPU-BT
OUT
F
When not executed 2.000 1.570
When executed
When displayed 53.100 38.090
Display completed 53.000 37.980
T(ST), C
When not executed 0.120 0.030
When executed
After time up 0.120 0.030
When added 0.120 0.030
SET F
When not executed 0.040 0.010
When executed
When displayed 52.000 40.600
Display completed 43.600 37.900
RST
F
When not executed 0.040 0.010
When executed
When displayed 45.700 36.600
Display completed 19.000 16.190
T(ST), C
When not executed 0.120 0.030
When executed 0.120 0.030

Table of Contents

Other manuals for Mitsubishi MELSEC Q Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC Q Series and is the answer not in the manual?

Mitsubishi MELSEC Q Series Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC Q Series
CategoryController
LanguageEnglish

Related product manuals