App-258
SD1614
Other system
error
information
category
Error
information
category
code
• This register stores the category code of error information
and individual information of the error that occurred on other
system.
• Data format is the same as SD4.
• The value in SD4 of the CPU module on other system is
reflected.
S
(Every END
processing)
SD4
QnPRH
SD1615
to
SD1625
Other system
error
common
information
Error
common
information
• Stores the common information corresponding to the error
code stored in this system CPU.
• Data composition is the same as SD5 to SD15.
• The values in SD5 to SD15 of the CPU module on other
system are reflected.
SD5 to
SD15
SD1626
to
SD1636
Other system
error
individual
information
Error
individual
information
• Stores the individual information corresponding to the error
code stored in this system CPU.
• Data composition is the same as SD16 to SD26.
• The values in SD16 to SD26 of the CPU module on other
system are reflected.
SD16 to
SD26
SD1649
Standby
system error
cancel
command
Error code of
the error to
be cleared
• This register stores the error code of the error to clear by
clearing a standby system error.
• The standby system error is cleared by turning SM1649 from
off to on after storing the error code of the error to clear.
• The least significant digit (ones place) of the error code in this
register is ignored.(The errors corresponding to error codes
4100 to 4109 are cleared by storing 4100 in this register.)
-
SD1650
Other system
operating
information
Other system
operating
information
This register stores the operating status of the CPU module on
the other system in the following bit pattern.
When communications with other systems are disabled or the
system is in the debug mode, "00FFH" is stored.
Note: Communications are disabled in the following states.
• The other system is powered off or is being reset.
• A hardware failure has occurred on the host or the other
system.
• A watchdog timer error has occurred on the host or the other
system.
• Tracking cable is not connected. Tracking cable is broken or
failed.
SD1690
Network
module head
address,
which
requested
system
switching on
host (control)
system
Network
module head
address,
which
requested
system
switching on
host (control)
system
• Stores head address of network module which a system
switch request was initiated, using the following format.
• Turns off automatically by system, after network error is reset
by user.
• To find the number for the module where system switching is
requested from a network module in the host system, refer to
SD1590.
S
(Every END
processing)
-QnPRH
Number Name Meaning Explanation
Set by
(When Set)
Corres-
ponding
ACPU
SD
*2
Corres-
ponding
CPU
b15 b8 b4b7 b3 b0
0
SD1650
0:No error
1:Continue error
2:Stop error
F:Communication with
other system
disabled
0:RUN
2:STOP
3:PAUSE
F:Communication with
other system
disabled
1 Communication
with other system
disabled, debug
mode
1
1
to to to
b1 b0b15 b11
0
0/10/10
SD1690
to
Module 0: CPU module is
invalid as it is 2-
slot model
Module 1: Module on right
side of CPU
module
Module11: Module at
rightmost end of
12-slot base
(Q312B)
Each bit
0:OFF
1:ON
to to

Table of Contents

Other manuals for Mitsubishi MELSEC Q Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC Q Series and is the answer not in the manual?

Mitsubishi MELSEC Q Series Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC Q Series
CategoryController
LanguageEnglish

Related product manuals