12-23
1
2
3
12
6
6
7
8
12.1 Error Code List
12.1.4 Error code list (2000 to 2999)
2040
[UNIT BAD CONNECT]
• The I/O module status is different from that
obtained at power-on.
• The I/O module (including the intelligent function
module) is nearly disconnected or is completely
disconnected during running.
â– Collateral information
• Common information: Module No. (Slot No.)
• Individual information:-
â– Diagnostic Timing
• Always
• Read common information of the error using
the programming tool to identify the numeric
value (module No.). Check the module
corresponding to the value and replace it as
necessary.
• Monitor SD1400 to SD1431 using the
programming tool to identify the module of
which data bit is "1". Check the module and
replace it as necessary.
• Reset the CPU module and run it again. If the
same error code is displayed again, the cause
is a hardware failure of the CPU module, I/O
module, intelligent function module, or END
cover. (Please consult your local Mitsubishi
representative, explaining a detailed
description of the problem.)
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
LCPU
2100
[SP. UNIT LAY ERR.]
The slot where the QI60 is mounted was assigned
as other than an intelligent function module or
interrupt module in the I/O assignment tab of the
PLC parameter dialog box.
â– Collateral information
• Common information: Module No. (Slot No.)
• Individual information:-
â– Diagnostic Timing
• At power-on/At reset
Make setting again to match the PLC parameter I/
O assignment with the actual loading status.
Qn(H)
*8
QnPH
QnPRH
[SP. UNIT LAY ERR.]
• The I/O module was assigned as an intelligent
function module in the I/O assignment tab of the
PLC parameter dialog box. Or vice versa.
• In the I/O assignment setting of PLC parameter,
a module other than CPU (or nothing) was
allocated to the location of a CPU module or
vice versa.
• In the I/O assignment setting of the PLC
parameter, switch setting was made to the
module that has no switch setting.
• In the I/O assignment setting of the PLC
parameter dialog box, the number of points
assigned to the intelligent function module is
less than the number of points of the mounted
module.
â– Collateral information
• Common information: Module No. (Slot No.)
• Individual information:-
â– Diagnostic Timing
• At power-on/At reset
• Make the PLC parameter's I/O assignment
setting again so it is consistent with the actual
status of the intelligent function module and the
CPU module.
• Delete the switch setting in the I/O assignment
setting of the PLC parameter.
Qn(H)
QnPH
QnPRH
QnU
[SP. UNIT LAY ERR.]
• In the I/O assignment tab of the PLC parameter
dialog box, the I/O module was assigned to the
slot for an intelligent function module. Or vice
versa.
• In the parameter I/O allocation settings, a
module other than CPU (or nothing) was
allocated to a location reserved for a CPU
module or vice versa.
• In the I/O assignment setting of the PLC
parameter dialog box, the number of points
assigned to the intelligent function module is
less than the number of points of the mounted
module.
â– Collateral information
• Common information: Module No. (Slot No.)
• Individual information:-
â– Diagnostic Timing
• At power-on/At reset
Reset the parameter I/O allocation setting to
conform to the actual status of the intelligent
function module and the CPU module.
Q00J/Q00/Q01
Error
Code
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU