12.1 Error Code List
12.1.4 Error code list (2000 to 2999)
2103
[SP. UNIT LAY ERR.]
Two or more QI60 modules where interrupt pointer
setting has not been made are mounted.
â– Collateral information
• Common information: Module No. (Slot No.)
• Individual information:-
â– Diagnostic Timing
• At power-on/At reset
• Reduce the QI60 modules to one.
• Make interrupt pointer setting to the second
QI60 module and later.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Q00J/Q00/Q01
*8
QnU
2106
[SP. UNIT LAY ERR.]
• Two or more MELSECNET/H modules are
mounted.
• Two or more CC-Link IE controller network
modules are mounted.
• Two or more Ethernet modules are mounted.
â– Collateral information
• Common information: Module No. (Slot No.)
• Individual information:-
â– Diagnostic Timing
• At power-on/At reset
• Reduce the number of MELSECNET/H
modules to one.
• Reduce the number of CC-Link IE controller
network modules to one.
• Reduce the number of Ethernet modules to
one.
Q00UJCPU
2106
[SP. UNIT LAY ERR.]
• Five or more MELSECNET/H and CC-Link IE
controller network modules in total are mounted
in the entire system.
• Two or more MELSECNET/H modules are
mounted in the entire system.
• Two or more CC-Link IE controller network
modules are mounted in the entire system.
• Two or more Ethernet modules are mounted in
the entire system.
â– Collateral information
• Common information: Module No. (Slot No.)
• Individual information:-
â– Diagnostic Timing
• At power-on/At reset
• Reduce the number of MELSECNET/H and
CC-Link IE controller network modules to four
or less in total in the entire system.
• Reduce the number of MELSECNET/H
modules to one in the entire system.
• Reduce the number of CC-Link IE controller
network modules to one in the entire system.
• Reduce the number of Ethernet modules to one
in the entire system.
Q00UCPU
Q01UCPU
[SP. UNIT LAY ERR.]
• Three or more MELSECNET/H and CC-Link IE
controller network modules in total are mounted
in the entire system.
• Three or more Ethernet interface modules are
mounted in the entire system.
â– Collateral information
• Common information: Module No. (Slot No.)
• Individual information:-
â– Diagnostic Timing
• At power-on/At reset
• Reduce the MELSECNET/H and CC-Link IE
controller network modules up to two or less in
the entire system.
• Reduce the Ethernet interface modules up to
two or less in the entire system.
Q02UCPU
[SP. UNIT LAY ERR.]
• Five or more MELSECNET/H and CC-Link IE
controller network modules in total are mounted
in the entire system.
• Five or more Ethernet interface modules are
mounted in the entire system.
â– Collateral information
• Common information: Module No. (Slot No.)
• Individual information:-
â– Diagnostic Timing
• At power-on/At reset
• Reduce the MELSECNET/H and CC-Link IE
controller network modules up to four or less in
the entire system.
• Reduce the Ethernet interface modules up to
four or less in the entire system.
QnU
*20
Error
Code
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU

Table of Contents

Other manuals for Mitsubishi MELSEC Q Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC Q Series and is the answer not in the manual?

Mitsubishi MELSEC Q Series Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC Q Series
CategoryController
LanguageEnglish

Related product manuals