12-36
2400
[FILE SET ERROR]
Automatic write to standard ROM was performed
on the CPU module that is incompatible with
automatic write to standard ROM.
(Memory card where automatic write to standard
ROM was selected in the boot file was fitted and
the parameter enable drive was set to the memory
card.)
â– Collateral information
• Common information: File name/Drive name
• Individual information:-
â– Diagnostic Timing
• At power-on/At reset/At writing to programmable
controller
• Execute automatic write to standard ROM on
the CPU module which is compatible with
automatic write to standard ROM.
• Write parameters and programs to the standard
ROM using the programming tool.
• Change the memory card for the one where
automatic write to standard ROM has not been
set, and perform boot operation from the
memory card.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Qn(H)
*8
QnPH
QnPRH
[FILE SET ERROR]
The file specified with a parameter does not exist.
â– Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
â– Diagnostic Timing
• At power-on/At reset/At writing to programmable
controller
• Read the individual information of the error
using the programming tool to identify the
numeric value (parameter No.). Check the drive
name and file name of the parameter
corresponding to the value, and correct it as
necessary.
• Create the specified file and write it to the CPU
module.
QCPU
LCPU
Error
Code
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU