EasyManuals Logo

Mitsubishi MELSEC Q Series Programming Manual

Mitsubishi MELSEC Q Series
1296 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #961 background imageLoading...
Page #961 background image
12-41
1
2
3
12
6
6
7
8
12.1 Error Code List
12.1.4 Error code list (2000 to 2999)
*1 CPU operations when an error occurred can be determined with a parameter. (LED indication varies according to the
CPU status.)
*6 Intelligent function module operations when an error occurred can be selected with a parameter from either to stop or
continue.
*7 This applies when the function version is A or later.
*8 This applies when the function version is B or later.
*10 This applies when the first five digits of the serial number is "04101" or later.
*15 This applies when the first five digits of the serial number is "09102" or later.
*17 This applies when the first five digits of the serial number is "10042" or later.
*18 This applies to the Universal model QCPU except for the Q00UJCPU.
*19 This applies to the Universal model QCPU except for the Q00UJCPU, Q00UCPU, and Q01UCPU.
*20 This applies to the Universal model QCPU except for the Q00UJCPU, Q00UCPU, Q01UCPU, and Q02UCPU.
*21 This applies to the Built-in Ethernet port QCPU.
2900
[DISPLAY ERROR]
The display unit was attached or detached while
the CPU module is on.
â– Collateral information
• Common information:-
• Individual information:-
â– Diagnostic Timing
• Always
• Do not detach the display unit during operation.
• Ensure that the display unit is securely
attached to the CPU module.
• Reset the CPU module and run it again. If the
same error is displayed again, the CPU module
or display unit is faulty. (Please consult your
local Mitsubishi representative, explaining a
detailed description of the problem.)
RUN:
On
ERR.:
On
CPU Status:
Continue
LCPU
2901
[DISPLAY ERROR]
A failure was detected in the display unit.
(in a initial processing)
â– Collateral information
• Common information:-
• Individual information:-
â– Diagnostic Timing
• At power-on/At reset
• Ensure that the display unit is securely
attached to the CPU module.
• Reset the CPU module and run it again. If the
same error code is displayed again, the cause
is a failure of the CPU module or display unit.
(Please consult your local Mitsubishi
representative, explaining a detailed
description of the problem.)
2902
[DISPLAY ERROR]
A failure was detected in the display unit.
(during operation)
â– Collateral information
• Common information:-
• Individual information:-
â– Diagnostic Timing
• Always
Error
Code
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU

Table of Contents

Other manuals for Mitsubishi MELSEC Q Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC Q Series and is the answer not in the manual?

Mitsubishi MELSEC Q Series Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC Q Series
CategoryController
LanguageEnglish

Related product manuals