12-57
1
2
3
12
6
6
7
8
12.1 Error Code List
12.1.5 Error code list (3000 to 3999)
*4 The parameter No. can be derived by "dividing the start I/O number of the intelligent function module set by GX
Configurator" by 10
H
.
*5 The diagnostic timing of CPU modules except for Universal QCPU and LCPU can be performed only when switching the
CPU module status from STOP to RUN.
*8 The function version is B or later.
*12 This applies when the first five digits of the serial number is "07032" or later.
*14 This applies when the first five digits of the serial number is "08102" or later.
*15 This applies when the first five digits of the serial number is "09102" or later.
*16 This applies when the first five digits of the serial number is "09082" or later.
*17 This applies when the first five digits of the serial number is "10042" or later.
*18 The Universal model QCPU except the Q00UJCPU.
*19 This applies to the Universal model QCPU except for the Q00UJCPU, Q00UCPU, and Q01UCPU.
*20 This applies to the Universal model QCPU except for the Q00UJCPU, Q00UCPU, Q01UCPU, and Q02UCPU.
3401
[REMOTE PASS. ERR.]
Any of the following modules is not mounted on the
slot specified for the head I/O number of the
remote password.
• Serial communication module of function
version B or later
• Ethernet module of function version B or later
• Modem interface module of function version B or
later
â– Collateral information
• Common information:-
• Individual information:-
â– Diagnostic Timing
• At power-on/At reset/STOP→RUN
Mount the following modules according to the
position specified with the start I/O number of the
remote password.
• Serial communication module of function
version B or later
• Ethernet module of function version B or later
• Modem interface module of function version B
or later
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Q00J/Q00/Q01
*8
[REMOTE PASS. ERR.]
Serial communication module, modem interface
module or Ethernet module of function version B or
later controlled by another CPU was specified in a
multiple CPU system.
â– Collateral information
• Common information:-
• Individual information:-
â– Diagnostic Timing
• At power-on/At reset/STOP→RUN
• Change it for the Ethernet module of function
version B or later connected by the host CPU.
• Delete the remote password setting.
Qn(H)
*8
QnPH
QnU
*18
Error
Code
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU