12.1 Error Code List
12.1.6 Error code list (4000 to 4999)
4353
[MULTI-COM. ERROR]
The device which cannot be used for the multiple
CPU high-speed transmission dedicated
instruction specified by the program is specified.
â– Collateral information
• Common information: Program error location
• Individual information:-
â– Diagnostic Timing
• When instruction executed
Read common information of the error using the
programming tool to identify the numeric value
(program error location). Check the error step
corresponding to the value, and correct it as
necessary.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
QnU
*20
4354
[MULTI-COM. ERROR]
The character string which cannot be handled by
the multiple CPU high-speed transmission
dedicated instruction is specified.
â– Collateral information
• Common information: Program error location
• Individual information:-
â– Diagnostic Timing
• When instruction executed
4355
[MULTI-COM. ERROR]
The number of read/write data (number of request/
receive data) for the multiple CPU high-speed
transmission dedicated instruction specified by the
program is not valid.
â– Collateral information
• Common information: Program error location
• Individual information:-
â– Diagnostic Timing
• When instruction executed
4400
[SFCP. CODE ERROR]
No SFCP or SFCPEND instruction in SFC
program.
â– Collateral information
• Common information: Program error location
• Individual information:-
â– Diagnostic Timing
•STOP→RUN
Write the program to the CPU module again using
the programming tool.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Qn(H)
QnPH
QnPRH
4410
[CAN'T SET(BL)]
The block number designated by the SFC program
exceeds the range.
â– Collateral information
• Common information: Program error location
• Individual information:-
â– Diagnostic Timing
• At power-on/At reset/STOP→RUN
Q00J/Q00/Q01
*8
Qn(H)
QnPH
QnPRH
QnU
LCPU
4411
[CAN'T SET(BL)]
Block number designations overlap in SFC
program.
â– Collateral information
• Common information: Program error location
• Individual information:-
â– Diagnostic Timing
• At power-on/At reset/STOP→RUN
4420
[CAN'T SET(S)]
A step number designated in an SFC program
exceeds the range.
â– Collateral information
• Common information: Program error location
• Individual information:-
â– Diagnostic Timing
• At power-on/At reset/STOP→RUN
Error
Code
(SD0)
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU

Table of Contents

Other manuals for Mitsubishi MELSEC Q Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC Q Series and is the answer not in the manual?

Mitsubishi MELSEC Q Series Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC Q Series
CategoryController
LanguageEnglish

Related product manuals