12-77
1
2
3
12
6
6
7
8
12.1 Error Code List
12.1.8 Error code list (6000 to 6999)
6101
[TRK. TRANS. ERR.]
• A timeout error occurred in tracking (data
transmission).
(This error may be caused by tracking cable
removal or other system power-off (including
reset).)
• The error occurred at a startup since the
redundant system startup procedure was not
followed.
(This can be detected from the control system or
standby system of the redundant system.)
â– Collateral information
• Common information: Tracking transmission
data classification
• Individual information:-
â– Diagnostic Timing
• Always
• Check the CPU module or tracking cable. If the
error still occurs, this indicates the CPU module
or tracking cable is faulty. (Please consult your
local Mitsubishi representative, explaining a
detailed description of the problem.)
• Confirm the redundant system startup
procedure, and execute a startup again.
RUN:
On
ERR.:
On
CPU Status:
Continue
QnPRH
6102
[TRK. TRANS. ERR.]
A data sum value error occurred in tracking (data
reception).
(This can be detected from the control system or
standby system of the redundant system.)
â– Collateral information
• Common information:-
• Individual information:-
â– Diagnostic Timing
• Always
6103
[TRK. TRANS. ERR.]
• A data error (other than sum value error)
occurred in tracking (data reception).
• (This error may be caused by tracking cable
removal or other system power-off (including
reset).)
• The error occurred at a startup since the
redundant system startup procedure was not
followed.
(This can be detected from the control system or
standby system of the redundant system.)
â– Collateral information
• Common information:-
• Individual information:-
â– Diagnostic Timing
• Always
6105
[TRK. TRANS. ERR.]
• An error (e.g. retry limit exceeded) occurred in
tracking (data transmission).
(This error may be caused by tracking cable
removal or other system power-off (including
reset).)
• The error occurred at a startup since the
redundant system startup procedure was not
followed.
(This can be detected from the control system or
standby system of the redundant system.)
â– Collateral information
• Common information: Tracking transmission
data classification
• Individual information:-
â– Diagnostic Timing
• Always
Error
Code
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU