[5-2 Outdoor Unit Control ]
- 95 -
HWE12050 GB
5 Control
5-2-14 Operation Mode
(1) Indoor unit operation mode
The operation mode can be selected from the following 5 modes using the remote controller.
(2) Outdoor unit operation mode
When the outdoor unit is performing a cooling operation, the operation mode of the connected indoor units that are not in the
cooling mode (Stopped, Fan, Thermo-OFF) cannot be changed to heating from the remote controller. If this attempt is mode,
"Heating" will flash on the remote controller. The opposite is true when the outdoor unit is performing a heating operation. (The
first selection has the priority.)
5-2-15 Demand Control
Cooling/heating operation can be prohibited (Thermo-OFF) by an external input to the indoor units.
When DIP SW6-8 is set to ON, the 4-step DEMAND control is enabled.
Eight-step demand control is possible in the system with two outdoor units.
Twelve-step demand control is possible in the system with three outdoor units.
For details, refer to the following page(s). [2-4-7 Various Control Methods Using the Signal Input/Output Connector on Outdoor
Unit](page 23)
1 Cooling mode
2 Heating mode
3 Dry mode
4Fan mode
5 Stopping mode
1 Cooling mode All indoor units in operation are in cooling mode.
2 Heating mode All indoor units in operation are in heating mode.
3 Stopping mode All indoor units are in fan mode or stopping mode.

Table of Contents