EasyManua.ls Logo

Mitsubishi PUHY-EP250 - Error Code [5110]; Error Code [5201]

Mitsubishi PUHY-EP250
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
[7-7 Error Code Definitions and Solutions: Codes [5000 - 5999] ]
- 175 -
HWE12050 GB
7 Troubleshooting Using Error Codes
7-7-3 Error Code [5110]
1. Error code definition
Heatsink temperature sensor (THHS) fault (Detail code 01)
2. Error definition and error detection method
When a short or an open of THHS is detected just before or during the inverter operation.
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-9 Troubleshooting Inverter Problems](page 234)
7-7-4 Error Code [5201]
1. Error code definition
High-pressure sensor fault (63HS1)
2. Error definition and error detection method
If the high pressure sensor detects 0.098MPa [14psi] or less during the operation, the outdoor unit stops once, turns to anti-
restart mode for 3 minutes, and restarts after 3 minutes when the detected high pressure sensor is 0.098MPa [14psi] or more.
If the high pressure sensor detects 0.098MPa [14psi] or less just before the restart, the outdoor unit makes an error stop, and
the error code "5201" will appear.
During 3-minute antirestart mode, preliminary errors will be displayed on the LED display.
A error is not detected for 3 minutes after the compressor start, during defrost operation, or 3 minutes after defrost operation.
3. Cause, check method and remedy
Cause Check method and remedy
(1) INV board failure If the problem recurs when the unit is put into operation, replace the INV board.
Cause Check method and remedy
(1) High pressure sensor failure Refer to the following page(s). [8-5-1 Com-
paring the High-Pressure Sensor Measure-
ment and Gauge Pressure](page 223)
(2) Pressure drop due to refrigerant leak
(3) Torn wire coating
(4) A pin on the male connector is missing or contact failure
(5) Disconnected wire
(6) High pressure sensor input circuit failure on the control board

Table of Contents