[6-3 Making the Group and Interlock Settings from an ME Remote Controller ]
- 105 -
HWE12050 GB
6 Test Run
6-3 Making the Group and Interlock Settings from an ME Remote
Controller
6-3-1 Overview
6-3-2 Address Registration
Make the following settings to perform a group operation of units that are connected to different outdoor units or to manually set up the
indoor/outdoor unit address.
(A) Group settings...........Registration of the indoor units to be controlled with the remote controller,
and search and deletion of registered information.
(B) Interlock settings........Registration of LOSSNAY units to be interlocked with the indoor units,
and search and deletion of registered information
[Normal display]
Register the indoor unit to be controlled with the remote controller.
Bring up either the blinking display of HO by turning on the unit or the
normal display by pressing the ON/OFF button.
The display window must look like one of the two figures below to proceed to the
next step.