EasyManua.ls Logo

Mitsubishi PUHY-EP250 - 9-1 LED Status Indicators

Mitsubishi PUHY-EP250
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
[8-10 Control Circuit ]
- 244 -
HWE12050 GB
2) PUHY-EP300 - EP450YKM-A
Outdoor unit
Power source system (380 ~ 415 VAC)
Control system (5 ~ 30 VDC)
* MA remote controllers and ME remote controllers cannot be used together.
(Both the ME and MA remote controller can be connected to a system with a system controller.)
A, B
A, B
M-NET
transmission line
(Non-polar 2 wire)
220 ~ 240 VAC
AC Power source
To next unit
(Indoor unit)
MA remote controller wiring
(Non-polar 2 wire)
17 ~ 30 VDC
9 ~ 12 VDC
TB2
TB15
Terminal block for
power source
TB5
Terminal block
for MA remote
controller
Terminal block
for transmission
line connection
17 ~ 30 VDC
Noise filter
Noise filter
Fuse Fuse
Fuse
72C, LEV
Fuse
Surge protection
INV board
Control board
Fan board
63H1
72C
DCL
DC / DC converter
Detection circuit for
the power supply to
the transmission line
M-NET board
DC / DC
converter
Microcomputer
Microcomputer
Microcomputer
5 V Power supply
16 V Power supply
12V Power supply
30 V Power supply
Relay drive circuit
Relay
5 V Power supply
5 V Power supply
17V Power supply
Smoothing capacitor
Inverter
Inverter
Inverter drive
circuit
Inverter drive
circuit
Inverter reset
circuit
Rectifier
Compressor
Heat
exchanger
fan 1
Heat
exchanger
fan 2
Relay, LEV
Drive circuit
Solenoid valve
4-way valve
CN40
Terminal block for
transmission line
for centralized control
(24 ~ 30 VDC)
TB7
Indoor/outdoor
transmission block
(24 ~ 30 VDC)
TB3
ME remote
controller
MA remote
controller
Indoor unit
Outdoor unit
Fuse
Fan board
Connect board
Microcomputer
5 V Power supply
16 V Power supply
Inverter
Inverter drive
circuit
Smoothing capacitor
Rectifier
380 ~ 415 VAC
Terminal block for
power source
TB1

Table of Contents

Related product manuals