2 Restrictions
2 Restrictions
2-1 System Configurations
1. Table of compatible indoor units
(1) High COP combinations
The table below summarizes the types of indoor units that are compatible with different types of outdoor units.
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
Outdoor units Composing units Maximum total
capacity of con-
nectable indoor
units
Maximum
number of
connect-
able indoor
units
Types of connectable
indoor units
EP200 YKM-A - - - 100 - 260 17
P15 - P200 models
R410A series indoor units
EP250 YKM-A - - - 125 - 325 21
EP300 YKM-A - - - 150 - 390 26
EP350 YKM-A - - - 175 - 455 30
P15 - P400 models
R410A series indoor units
EP400
YKM-A - - -
200 - 520 34
P15 - P500 models
R410A series indoor units
YSKM-A EP200 EP200 -
EP450
YKM-A - - -
225 - 585 39
YSKM-A EP250 EP200 -
EP500 YSKM-A EP300 EP200 - 250 - 650 43
EP550 YSKM-A EP300 EP250 - 275 - 715 47
EP600 YSKM-A EP300 EP300 - 300 - 780 50
EP650 YSKM-A EP250 EP200 EP200 325 - 845
EP700 YSKM-A EP300 EP200 EP200 350 - 910
EP750 YSKM-A EP300 EP250 EP200 375 - 975
EP800 YSKM-A EP300 EP300 EP200 400 - 1040
EP850 YSKM-A EP300 EP300 EP250 425 - 1105
EP900 YSKM-A EP300 EP300 EP300 450 - 1170