[6-11 Standard Operation Data (Reference Data) ]
- 139 -
HWE12050 GB
6 Test Run
Packaged unit model PUHY-EP800YSKM-A
Outdoor unit model PUHY-EP200YKM-A PUHY-EP300YKM-A PUHY-EP300YKM-A
Conditions
Ambient temperature
(cooling)
Indoor
DB/WB
26.7°C/19.4°C [80°F/67°F]
Outdoor 35°C/- [95°F/-]
Ambient temperature
(heating)
Indoor
DB/WB
21.1°C/- [70°F/-]
Outdoor 8.3°C/6.1°C [47°F/43°F]
Indoor unit
Number of units connected
Unit
6
Number of units in operation 6
Model - 125/125/125/140/140/140
Piping
Main pipe
m [ft]
5 [16-3/8]
Branch pipe 10 [32-3/4]
Total pipe length 65 [213-1/4]
Fan speed - Hi
Refrigerant charge kg [lbs-oz] 62 [137]
Outdoor unit Voltage V 400
Cooling operation
Outdoor unit
Electric current A 72.0
Compressor frequency Hz 52 74 74
LEV open-
ing
Indoor unit
Pulse
387/387/387/310/310/310
SC (LEV1) 141 185 185
LEV2 2100 2100 2100
Pressure High pressure (after O/S)/Low pressure (before accumulator) MPa [psi]
2.82/0.92 2.82/0.92 2.82/0.92
[408/134] [408/134] [408/134]
Section
tempera-
tures
Outdoor unit
Discharge (TH4)
°C [°F]
69 [156] 73 [163] 73 [163]
Heat exchanger outlet (TH3) 44 [111] 40 [104] 40 [104]
Accumulator inlet 10 [50] 10 [50] 10 [50]
Accumulator outlet 10 [50] 10 [50] 10 [50]
SCC outlet (TH6) 24 [75] 20 [68] 20 [68]
Compressor inlet 17 [63] 15 [59] 15 [59]
Compressor shell bottom 47 [117] 42 [108] 42 [108]
Indoor unit
LEV inlet 20 [68] 20 [68] 20 [68]
Heat exchanger outlet 10 [50] 10 [50] 10 [50]
Heating operation
Outdoor unit
Electric current A 76.1
Compressor frequency Hz 53 81 81
LEV open-
ing
Indoor unit
Pulse
406/406/406/414/414/414
SC (LEV1) 0
LEV2 2100 2100 2100
Pressure High pressure (after O/S)/Low pressure (before accumulator) MPa [psi]
2.66/0.66 2.66/0.66 2.66/0.66
[387/95] [387/95] [387/95]
Section
tempera-
tures
Outdoor unit
Discharge (TH4)
°C [°F]
72 [162] 70 [158] 70 [158]
Heat exchanger outlet (TH3) 0 [32] -1 [30] -1 [30]
Accumulator inlet 0 [32] -1 [30] -1 [30]
Accumulator outlet 0 [32] -1 [30] -1 [30]
Compressor inlet 0 [32] -1 [30] -1 [30]
Compressor shell bottom 40 [104] 40 [104] 40 [104]
Indoor unit
LEV inlet 36 [97] 36 [97] 36 [97]
Heat exchanger inlet 69 [157] 69 [157] 69 [157]