6 - 54 6 - 54
MELSEC-Q
6 DEDICATED INSTRUCTIONS
Control data
Device Item Set data Setting range
Set by (
1
)
(S1) + 0
Execution/abnormal
complete type
b15 b7 b0to to
01)2) 0
1) Execution type (bit 0)
0: No arrival confirmation
When the target station is on the same network:
Completed when the data is sent from the local
station.
Execution source Target station
Complete
When the target station is on other network:
Completed when the data arrives at the relay
station on the network of the local station.
Relay stationExecution source Target station
Complete
1: With arrival confirmation
Completed when data is written to the target
station.
Relay station
Target station
Complete
Execution source
Complete
Target station
2) Abnormal complete type (bit 7)
Designate whether the clock data setting is required
or not at abnormal completion.
0: Clock data setting not required:
Clock data at error occurrence is not stored in
(S1) + 11 to (S1) + 17.
1: Clock data setting required
Clock data at error occurrence is stored in (S1)
+ 11 to (S1) + 17.
0001
H
0081
H
User
(S1) + 1 Completion status
Stores the status at the completion of the instruction.
0
: Normal
Other than 0: Abnormal (error code) (
2
)
—System
(S1) + 2
Channel used by the local
station
Set the channel used by the local station.
1 to 8 (channel)
1 to 8 User
Specify the CPU type on the target station.
Setting value Description
0000
H
Single CPU or CPU in the system
directly connected to the local station
(Same as "03FF
H
")
03D0
H
Control system CPU (
5
)
03D1
H
Standby system CPU (
5
)
03D2
H
System A CPU
03D3
H
System B CPU
03FF
H
Single CPU or CPU in the system
directly connected to the local station
(S1) + 3
Target station’s CPU type
(
3
)
0000
H
03D0
H
to
03D3
H
03FF
H
User
(S1) + 4
Target station network
number
Designate the network number of the target station.
1 to 239: Network number
254
: When 254 is designated in Jn (The network
designated by the valid module during other
station access)
1 to 239, 254 User
(Continued to the next page)