EasyManua.ls Logo

molex BradControl HarshIO 600 eIP - Page 29

molex BradControl HarshIO 600 eIP
97 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
HarshIO 600 eIP
29
IP67 Digital I/O Modules for EtherNet/IP
16 Inputs module versions
Byte
Offset
Bit 15
Bit 14
Bit 13
Bit 12
Bit 11
Bit 10
Bit 9
Bit 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Input Data (Assembly #103), Size: 8 bytes
Data
00
n/u
n/u
n/u
n/u
n/u
n/u
Diag
UB
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
Input Data
02
I15
I14
I13
I12
I11
I10
I9
I8
I7
I6
I5
I4
I3
I2
I1
I0
Port Status
04
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
Port Status
06
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
PS P7
PS P6
PS P5
PS P4
PS P3
PS P2
PS P1
PS P0
Output data (Assembly #104), Size: 2 bytes
Output Data
00
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
Configuration (Assembly #106), Size: 16 bytes
Data
00
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
Data
02
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
Data
04
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
Data
06
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
Data
08
n/u
n/u
n/u
n/u
n/u
n/u
n/u
QC
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
Data
10
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
Data
12
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
Data
14
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u
n/u: Not used
Ix: Input channel x
PS: Port Status (short circuit detected on a port driving Input channels)
QC: Quick Connect, 1 = Enable; 0 = Disable
Diag UB: Diagnostic Logic/Input power supply (UB)
Set to 1, if UB is < 14.1 VDC
o All Outputs activated are de-energized
o All Outputs activated have diagnostic leds to RED
o All Outputs activated have Port Status (CS Ox) bit set to 1
Set to 0, if UB is > 14.6 VDC
o All Outputs activated are energized
o All Outputs activated have diagnostic leds to GREEN
o All Outputs activated have Port Status (CS Ox) bit set to 0

Table of Contents