ioLogik E1200 Series Modbus/TCP Default Address Mappings
Parameter Name Description Start
Address
(decimal)
Point
Type
Start
Register
(decimal)
Length Access Type
lanMac e.g.
00:90:E8:3E:
18:CC -> 1st
byte: 0, 2nd
byte: 144, 3rd
byte: 232, 4th
byte: 62, 5th
byte: 24, 6th
byte: 204
5024 04:INPUT
REGISTER
35025 3 R word
modelName Each byte
represents
ASCII code of
each character
5000 04:INPUT
REGISTER
35001 10 R word
watchdogAlarmFlag 1: clear
watchdog
alarm
4144 01:COIL
STATUS
04145 1 R/W bit
ioLogik E1260 Modbus Address and Register
Map
I/O
Parameter Name Description Start
Address
(decimal)
Point
Type
Start
Register
(decimal)
Length Access Type
RTD_multipliedEngin
eeringValue
Unit: 0.1 1536 04:INPUT
REGISTER
31537 6 R word
RTD_multipliedEngin
eeringValueMax
high/low word 1572 04:INPUT
REGISTER
31573 6 R word
RTD_multipliedEngin
eeringValueMin
high/low word 1560 04:INPUT
REGISTER
31561 6 R word
RTD_resetMaxValue 1: reset max.
value
4169 01:COIL
STATUS
04170 6 R/W bit
RTD_resetMinValue 1: reset min.
value
4161 01:COIL
STATUS
04162 6 R/W bit
RTD_scaledValue high/low word 1548 04:INPUT
REGISTER
31549 12 R 2 words
RTD_scaledValueMax high/low word 1596 04:INPUT
REGISTER
31597 12 R 2 words
RTD_scaledValueMin high/low word 1584 04:INPUT
REGISTER
31585 12 R 2 words