ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-12
Parameter Name Description Start
Address
(decimal)
Point
Type
Start
Register
(decimal)
Length Access Type
lanIp e.g.
192.168.127.2
54 -
> 1st byte:
192, 2nd byte:
168, 3rd byte:
127, 4th byte:
254
5027 04:INPUT
REGISTER
35028 2 R word
lanMac e.g.
00:90:E8:3E:1
8:CC -> 1st
byte: 0, 2nd
byte: 144, 3rd
byte: 232, 4th
byte: 62, 5th
byte: 24, 6th
byte: 204
5024 04:INPUT
REGISTER
35025 3 R word
modelName Each byte
represents
ASCII code of
each character
5000 04:INPUT
REGISTER
35001 10 R word
ioLogik E1241 Modbus Address and Register
Map
I/O
Parameter Name Description Start
Address
(decimal)
Point
Type
Start
Register
(decimal)
Length Access Type
AO_p2pSafeModeFla
gClear
1: clear safe
mode flag
4128 01:COIL
STATUS
04129 4 R/W bit
AO_p2pSafeModeFla
g
0: OFF, 1: ON 4112 02:INPUT
STATUS
14113 4 R bit
AO_p2pStatus 0: OFF, 1: ON 4096 02:INPUT
STATUS
14097 4 R bit
AO_rawValue 1024 03:HOLDI
NG
REGISTER
41025 4 R/W word
AO_scaledValue high/low word 0000 04:INPUT
REGISTER
30001 8 R 2 words

Table of Contents

Other manuals for Moxa Technologies ioLogik E1211

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Moxa Technologies ioLogik E1211 and is the answer not in the manual?

Moxa Technologies ioLogik E1211 Specifications

General IconGeneral
BrandMoxa Technologies
ModelioLogik E1211
CategoryI/O Systems
LanguageEnglish

Related product manuals