11 Technical data
104 5831400/02 EN
Utilization category in accordance with IEC60947‑5‑1
Utilization cate-
gory in accor-
dance with
IEC60947‑5‑1
Typical application Rating/nominal
operation
U
N
I
N
AC-12
(50/60Hz)
Regulation of resistive load and semi-con-
ductor load resistance with disconnection
via optocoupler
230V 5A
AC-15
(50/60Hz)
Regulation of electromagnetic load resis-
tance with AC voltage
230V 0.26A
120V 0.5A
24V 2A
DC-12 Regulation of resistive load and semi-con-
ductor load resistance with disconnection
via optocoupler
220V 0.2A
120V 0.4A
30V 5A
DC-13 Regulation of electromagnets with DC volt-
age
220V 0.11A
120V 0.21A
24V 1.04A
Switching capacity in accordance IEC60076-22-1
Micro-switch version U
N
Switching capacity in accordance
IEC60076-22-1
Standard switch 230VAC Making capacity: 250VA, cosφ>0.5
Breaking capacity: 60VA, cosφ>0.5
24…
220VDC
Making capacity: 130W, L/R<40ms
Breaking capacity: 25W, L/R<40ms
Switch with gold-plated con-
tacts
1)
230VAC Max. 6.9VA, cosφ=0.9
24…
220VDC
Max.6.6W, L/R<25ms
1)
Switching higher loads destroys the gold plating.