11 Technical data
1075831400/02 EN
Address Data type Designation
17 UINT16 Firmware version major
18 UINT16 Firmware version minor
19 UINT16 Firmware version patch
Table15: Input register
With FLOAT parameters, the MSB (Most Significant Bit) is stored in the
lower address and the LSB (Least Significant Bit) in the higher address.
Configuration via holding register
Each address must be unique in the BUS system. Therefore,
for example, when using two identical devices (same default
address!), configure them to different addresses before com-
missioning!
Use function code "03" to read the information and function code "06/16" to
write the information.
Address Data type Designation Setting option
0 UINT16 Modbus address 1…247
21
1)
(oil temperature indicator)
22
1)
(winding temperature indi-
cator)
1 UINT16 Modbus baud rate 0: 4800
1: 9600
2: 19200
1)
3: 38400
4: 57600
5: 115200
2 UINT16 Modbus parity 0: None
1: Even
1)
2: Odd
3 - Reserved -
4 - 4...20mA analog output 0: Deactivated
1: Activated
1)2)