Accessories
PrimaX
60
GB
8 Accessories
For part numbers chapter 8.7.
8.1 Calibration Cap
Using calibration cap allows span gas calibration procedure to be accurate in
windy environmental conditions.
The calibration cap is pushed on to the front of the sensor and is sealed by an
O- ring. The surface area S < 20 cm
2
.
Fig. 13 Calibration cap
8.2 Sensor Gard
Fig. 14 Sensor gard
The sensor gard should be fitted at all times except when using the flow through
adapter or duct mount kit.
Ambient weather condition can affect the gas mixture inside of the sensor gard. Use
sensor gard for functional test only. Calibration cap is recommended for sensor cal-
ibration.
Warning!
The calibrating cap must be removed after completing the calibration!
The gas is supplied via either of the gas inlets by means of suitable flex-
ible tube.