35
Operation
Setup Relay State for Energized or De-Energized
The relay configuration from the factory should not be altered as it will cause undesirable
operation of the local strobes, horn and pushbutton.
Analog Output Settings for Fault Conditions
Analog outputs can be set to 3.5 mA and 1.25 mA with HART, or to custom output values as listed
in Tab. 13. Output settings for oxygen sensors are not configurable. The Maintenance analog
output is used during start up, Reset Main Unit, and Controller Data Reset.
To change Analog outputs settings:
(1)
Scroll to Settings.
(2)
Select Instruments.
(3)
Scroll and Select Analog Settings.
(4)
Select 3.5, 1.25, Custom 1 or Custom 2.
(5)
Select Save.
(6)
(Only Custom) Select Fault, Calibration, or Maintenance.
(7)
(Only Custom) Enter desired output levels (options in Tab. 13).
(8)
(Only Custom) Select Save.
(9)
(Only Custom) Repeat for remaining outputs.
(10)
Select Save.
US