Table 5 Maximum Wire Length to Main Transmitter with Two Remoted Sensors, Imperial Units
Sensor
Mounting
Sensor1 Sensor2 Max.
Power
1
(W)
Max.Distance(ft)totransmitter
24VDCSupply
18AWG 16AWG 14AWG 12AWG
Two
sensors
mounted
onjunction
boxupto
328ft
for24V
Echem Echem 3.6 2079 3134 4992 7932
Catalytic 5.3 1421 2173 3492 5576
XIRPLUS 7.0 962 1516 2481 4004
Catalytic Echem 5.3 1421 2173 3492 5576
Catalytic 10.6 1104 1691 2721 4348
XIRPLUS 10.9 743 1205 2009 3275
XIR
PLUS
Echem 7.0 962 1516 2481 4004
Catalytic 10.9 743 1205 2009 3275
XIRPLUS 11.6 711 1115 1823 2941
1
Whensizingasystem's24Vsupply,a1Ainrushcurrentwitha1msdurationshouldbeconsideredforeach
ULTIMA
X5000onthepowersupply.
Assumestransmitterwasorderedwithrelays
Table 6 Maximum Wire Length to Main Transmitter with Two Remoted Sensors, Metric Units
Sensor
Mounting
Sensor1 Sensor2 Max.
Power
1
(W)
Max.Distanceinmeters
24VDCSupply
0.75mm
2
1mm
2
1.5mm
2
2.5mm
2
4mm
2
Two
sensors
mounted
onjunction
boxupto
100m
Echem Echem 3.6 560 747 1122 1869 2881
Catalytic 5.3 381 515 781 1310 2028
XIR
PLUS
7.0 255 353 549 936 1461
Catalytic Echem 5.3 381 515 781 1310 2028
Catalytic 10.6 296 400 608 1022 1582
XIR
PLUS
10.9 194 277 440 762 1198
XIR
PLUS
Echem 7.0 255 353 549 936 1461
Catalytic 10.9 194 277 440 762 1198
XIR
PLUS
11.6 189 260 403 688 1073
1
Whensizingasystem's24Vsupply,a1Ainrushcurrentwitha1msdurationshouldbeconsideredforeach
ULTIMA
X5000onthepowersupply.
Assumestransmitterwasorderedwithrelays
29 Ultima X5000 Gas Monitor US
3 Installation