Digital inputs Digital inputs can be wired to allow the input from a switch
contact, a relay contact, or a logic signal.
All digital inputs are optically isolated at the 498 Digital I/O
transition module.
For example, an action defined in the can be selected, in the
Station Setup window’s Digital Input panel, as an Action
The digital inputs are used by the Digital Input process in the
MultiPurpose TestWare application. They can also be monitored
from the Station Manager application.
You can use the Event-Action Editor window to define an action
that occurs in response to a digital input event. The defined action
can then be selected in the Station Setup window’s Digital Input
panel.
Sixteen jumpers located on the 498 Digital I/O transition module
allow each input to be configured for a relay contact or logic signal.
Each digital input connector on the built-in Digital I/O Access panel
(FlexTest IIm) supports two channels.
Each digital input supports a differential TTL to +30 V DC signal or
a switch or relay contact switching the on-board 12 V supply.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the MTS Systems FlexTest IIm and is the answer not in the manual?

MTS Systems FlexTest IIm Specifications

General IconGeneral
BrandMTS Systems
ModelFlexTest IIm
CategoryController
LanguageEnglish

Related product manuals