Specifications
Description Specification
Input Power Voltage
100 – 240 VAC
50/60 Hz
Input AC Power 0.75A (at full load (meaning Wi-Fi, internet, cell phone,
and 20 relays ON))
Relays
1 Amp. Up to 60% of the relays can operate at any given
time.
Note: Running relays at the above current levels provides between 50,000 –
100,000 switching operations.
Analog Inputs 0 – 3.3 Volts
Analog Output 0 - 10 Volts; maximum load: 20 mA
Digital Inputs 3.3 Volts, 1.5 mA, dry contact
Communication
LAN – Standard 10/100 BaseT
Expansion – RS-485: 115 Kbps, 8 bit, even parity
Operating and Storage
Temperature Range
-10° to +50° C (+14° to +125° F)
Environmental
Specifications
Altitude: -400 m to 2000 m
Relative Humidity: 20% - 70%
Main supply voltage fluctuation up to 5%
Overvoltage category II
Enclosure
Water and dust tight
Indoor use only
Dimensions (H/W/D) 403 x 324 x 141 mm/16 x 13 x 5.6 inches
Fuses Fuse F2 on PS card: 3.15A, 250V
Certification
•
Disconnection device/overcurrent protection: In the building installation, use a
certified 2-pole circuit breaker rated 10A, certified in accordance with the IEC
standard 60947-2 (in the US and Canada use a Listed Brach Circuit protective
circuit breaker). This step is required to provide overcurrent protection and mains
disconnection. The circuit breaker must be easily accessible and marked as the
controller disconnect device.
•
Main Supply Voltage: Permanently connect the controller to the mains in
accordance with the relevant national code. Provide fixed wiring inside a flexible
conduit. Relays must be suitably protected against overcurrent, using a circuit
breaker rated at 10A.