© Munters AB, 2020 72
6. Go to Climate > Static Pressure and define the parameters.
7.15.2 S
TATIC
P
RESSURE
C
ALIBRATION
CAUTION
The Static Pressure sensor is factory calibrated. Only calibrate the sensor if you
have reason to believe that they are producing inaccurate results.
The Static Pressure should be 0 when there is no ventilation and the house is closed. When
the controller A/D counts is 100, this means that there is zero (0) static pressure.
NOTE: Run the controller for a few hours so that the temperature in the box becomes
stable and only then calibrate.
CAUTION
DO NOT blow the air into the hose to see of the pressure changes! The sensor is
sensitive and blowing air can cause irreparable damage.
To calibrate the Static Pressure Sensor:
1. Disconnect the air hoses.
2. Go to System > Device & Sensors > Pressure.