© Munters AB, 2020 47
3. Edit the parameters.
o
Capacity: Enter the fan capacity.
o
KWh: This field displays the amount of kilowatts used. Read-only.
o
Operation: Select if the relay is normally open or normally close.
4. Click Save.
7.3.1.2 0 – 10 Volt Fans
1. On the Device and Sensors screen, click a fan analog output port.
2. Click .
3. Edit the parameters.
o
Minimum/Maximum Voltage: Enter the minimal and maximal voltage used to
calibrate the fan speed. For example, if the minimum voltage is set to 2V and
the maximum to 8V the controller applies the calculated 0-100% output over
a 2V-8V signal.
o
Capacity: Enter the fan capacity.
o
KWh: This field displays the amount of kilowatts used. Read-only.
o
Boost Time: During this amount of time, the controller applied full power to
the fan motor (100%).
4. Click Save.
5. To test in the minimal and maximum voltages, click Test.