Section 75 00-02-0522
04-06-11 - 15 -
c
Deere
k
Lister-Petter
d
Detroit
l
Mercedes
e
Deutz
m
Perkins
f
Ford
n
Volvo
g
GM
o
Other (Default)
h
Hatz
NOTE: Caterpillar, Cummins, Deere, Detroit, Deutz, Ford, GM, Hatz, Isuzu,
Kubota, Lister-Petter, Mercedes, Perkins, Volvo are registered trademarks of
their respective corporations
5. J1939 Crankcut Count - Is the number of consecutive measurements of the RPM above
the Crankcut RPM, required to achieve crank disconnect.
6. Fuel Level Source - Select level source.
a. None (Default)
b. J1939
c. Analog Input
7. Oil Life - Sets service interval timer for end user maintenance reminder. (Default 100
hours)
8. Oil Filter Life - Sets service interval timer for end user maintenance reminder. (Default 100
hours)
9. Belt Life - Sets service interval timer for end user maintenance reminder. (Default 100
hours)
10. Battery Life - Sets service interval timer for end user maintenance reminder. (Default 100
hours)
11. Fuel Filter Life - Sets service interval timer for end user maintenance reminder. (Default
100 hours)
12. Air Filter Life - Sets service interval timer for end user maintenance reminder. (Default
100 hours)
13. Overhaul Life - Sets service interval timer for end user maintenance reminder. (Default
1000 x 10 hours)