Section 75 00-02-0522
04-06-11 - 22 -
 Digital Input 8 - User Input 6.
 Digital Input 9 - Remote Call to Run. (Transfer switch input)
 Digital Input 10 - Low Lubrication Oil Level.
 Digital Input 11- Low Coolant Level.
 Digital Input 12 - Low Fuel Level Warning.
 Digital Input 13 - Fuel Leak.
 Digital Input 14 - Battery Charger AC Fail.
 Digital Input 15 - Emergency Stop N/O.
 Digital Input 16 - Air Damper Closed.
 Digital Input 17 - Generator Config 1.
 Digital Input 18 - Generator Config 2.
 Digital Input 19 - Generator Config 3.
 Digital Input 20 - Generator Config 4.
 Digital Input 21 - Generator Config 5.
 Digital Input 22 - Generator Config 6.
 Digital Input 23 - Fuel Filter Restriction.
 Digital Input 24 - Air Filter Restriction.
Menu Selections for Digital Inputs
1. Disabled - Not used
2. Remote Call to Run - In automatic mode, when this input is grounded, the system will
initiate an automatic start sequence.
3. Remote Alarm Acknowledge - When grounded will acknowledge (silence) remote audible
alarms.
4. Engine Overspeed - When grounded, initiates an immediate shutdown and lockout and
displays "Engine overspeed" as cause of shutdown.
5. Crank Termination - When active will cause immediate cessation of cranking, and no
cranking can occur while this input is active.