NESS D16 (V4.6) CONTROL PANEL - INSTALLER MANUAL
DAY ZONE FOLLOWER
This option allows Day zones to appear on the Zone Outputs.
In Day mode the Zone Output will follow the state of any active Day zone. This
occurs independently of the Program Zone selections P118E (Output Expander
Zone Follower) and P119E (Output Expander Zone Latch).
PROGRAMMING SEQUENCE:
P117E 3E toggles the option ON and OFF
P117E 3E OFF: No Day Zone Follower
P117E 3E ON: Day Zone Follower enabled
P117E 3E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
OFF: No Day Zone Follower
NOTES:
Day zone outputs are turned off when the
D16 is in Monitor or Area modes.
OUTPUT EXCLUDE
This allows zones selected for Manual Exclusion (not Auto Exclusion) to also
Exclude the Expander Zone outputs. With this option ON, and if a zone has
been manually excluded then it will not signal an alarm on the Expander.
PROGRAMMING SEQUENCE:
P117E 4E toggles the option ON and OFF
P117E 4E OFF: No Output Exclude
P117E 4E ON: Output Exclude enabled
P117E 4E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
OFF: No Output Exclude
NOTES:
OUTPUT EXPANDER ZONE FOLLOWER
This selects the zones that will be output whenever the zone is unsealed. When
the zone reseals the output automatically goes off.
Additionally if a zone is also selected in P119 (to zone latch) then an output will
only occur whenever a zone is in alarm and is also unsealed. In this case when
the zone reseals the output automatically goes off again. A further zone unseal
will turn the zone Expander output On again.
PROGRAMMING SEQUENCE:
P118E 1E-16E toggles the option ON and OFF
P118E 1E-16E OFF: Output Expander disabled for that zone
P118E 1E-16E ON: Output Expander enabled for that zone
P118E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
OFF: No Output Expander zones
NOTES:
Selecting a zone in both P118 & P119
options effectively gives pulsed outputs
whenever that zone alarms.
OPTION No DESCRIPTION 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Zones
ON = Factory default setting
P118E O/P Expander zones
P119E
O/P Expander alarm zones
OUTPUT EXPANDER ZONE LATCH
This selects the zones that will be output whenever the zone is latched into
alarm. The output goes off only when the alarm system is reset.
Additionally if a zone is also selected in P118 (to zone follow) then an output
will only occur whenever a zone is in alarm and is also unsealed. (See P118
above).
PROGRAMMING SEQUENCE:
P119E 1E-16E toggles the option ON and OFF
P119E 1E-16E OFF: Output Expander zone alarm disabled for that zone
P119E 1E-16E ON: Output Expander zone alarm enabled for that zone
P119E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
OFF: No Output Expander zone latch
NOTES:
D16 OUTPUT EXPANDER
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ness D-16 and is the answer not in the manual?

Ness D-16 Specifications

General IconGeneral
BrandNess
ModelD-16
CategoryControl Panel
LanguageEnglish

Related product manuals