6.3.8 Refrigeration system failure (Ct)
Display
Description
Denes the maximum continuous runtime of the compressor without reaching the set
point (SP) temperature.
If the set point (SP) temperature is not reached within this time, the controller enters
the RSF Limp home mode.
Considerations None
Range 0 to 100 hours
Global default 72 hours
6.3.9 Celsius or Fahrenheit (CF)
Display
Description Option to set the EMS controller to Celsius (°C) or Fahrenheit (°F).
Considerations
• A global reset sets EMS controllers using Fahrenheit (°F) to Celsius (°C).
• Applies to all temperature settings and values.
Range 0 (°C) or 1 (°F)
Global default 0 (°C)
6.3.10 Saving dierential (Sd)
Display
Description
Denes the compressor cut-in temperature, when added to the saving set point (SSP)
temperature, during the Saving mode.
Considerations
If the saving dierential (Sd) is set too low, for example less than 2.0°C, the
compressor may cycle on the minimum compressor rest time (rt).
Range 0.0 to 9.9°C (0 to 18°F)
Global default 4.0°C (7°F)