6.3.11 Saving set point (SSP)
Display
Description Denes the compressor cut-out temperature during the Saving mode.
Considerations Must be set above the set point (SP).
Range 0.0 to 9.9°C (32 to 50°F)
Global default 7.0°C (45°F)
6.3.12 Uninterrupted pull down (IPd)
Display
Description
Denes the temperature that if exceeded starts an uninterrupted pull down, i.e. the
controller switches on the compressor and runs the compressor continuously until the
product reaches the set point (SP) temperature.
During this time, defrost cycles do not occur.
Considerations
Must be set as follows:
• Above the saving set point (SSP) plus saving dierential (Sd) temperature.
• Above the defrost termination (dtd) temperature.
• Not used on Sub-Zero version
Range 0.0 to 60ºC (32 to 140ºF)
Global default 20ºC (68ºF)
6.3.13 Freeze-up protection (dtt)
Display
Description
Denes the temperature to stop further cooling to prevent freeze-up due to low
temperature.
Considerations Must be set below the set point (SP) temperature.
Range -10 to 10ºC (14 to 50ºF)
Global default 0.0ºC (32ºF)