6.3.14 Defrost interval (dE)
Display
Description
Denes the period between the end of defrost cycle and beginning of the next defrost
cycle. A time-based defrost cycle helps improve evaporator eciency.
Considerations
In the event of power loss, the defrost interval (dE) is not maintained. The defrost
interval is reset.
If icing up occurs, review the values of the defrost parameters.
Range 0 to 199 hours
Global default 6 hours
6.3.15 Defrost duration (dd)
Display
Description Denes the maximum time of a defrost cycle.
Considerations If icing up occurs, review the values of the defrost parameters.
Range 1 to 199 minutes
Global default 15 minutes
6.3.16 Fan cycle on (FCO)
Display
Description Denes the active period of the evaporator fan while the compressor is switched o.
Considerations Fan cycle is the fan cycle on (FCO) time + the fan cycle o (FCF) time.
Range 1 to 30 minutes
Global default 30 minutes