Product Manual, Issue 8 CMS100
www.nexo.comPage 50
6.3.17 Fan cycle o (FCF)
Display
Description Denes the inactive period of the evaporator fan while the compressor is switched o.
Considerations Fan cycle is the fan cycle on (FCO) time + the fan cycle o (FCF) time.
Range 0 to 30 minutes
Global default 1 minute
6.3.18 Alarm delay (Ad)
Display
Description
Denes the maximum time the cooler door can be open before sounding the alarm
buzzer.
Considerations
If disabled, the door switch is also disabled - if so the controller does not detect door
openings therefore, it does not:
Update the self-learning matrix for door activity.
Manage the evaporator fan for door activity.
Sound door alarms if the door is left open.
Range 0 to 30 minutes
Global default 0 (disabled)
6.3.19 Buzzer duration (b1)
Display
Description
Denes the duration of the buzzer for door open alarm conditions.
If the door remains open after the buzzer duration (b1), the controller switches o the
compressor for the duration of RT before starting door open limp home mode.
Considerations
The controller switches o the compressor after the duration dened by alarm delay
(Ad) + buzzer duration (b1 ).
Range 1 to 254 seconds
Global default 60 seconds