Product Manual, Issue 8 CMS100
www.nexo.comPage 50
6.3.17 Fan cycle o (FCF)
Display
Description Denes the inactive period of the evaporator fan while the compressor is switched o.
Considerations Fan cycle is the fan cycle on (FCO) time + the fan cycle o (FCF) time.
Range 0 to 30 minutes
Global default 1 minute
6.3.18 Alarm delay (Ad)
Display
Description
Denes the maximum time the cooler door can be open before sounding the alarm
buzzer.
Considerations
If disabled, the door switch is also disabled - if so the controller does not detect door
openings therefore, it does not:
• Update the self-learning matrix for door activity.
• Manage the evaporator fan for door activity.
• Sound door alarms if the door is left open.
Range 0 to 30 minutes
Global default 0 (disabled)
6.3.19 Buzzer duration (b1)
Display
Description
Denes the duration of the buzzer for door open alarm conditions.
If the door remains open after the buzzer duration (b1), the controller switches o the
compressor for the duration of RT before starting door open limp home mode.
Considerations
The controller switches o the compressor after the duration dened by alarm delay
(Ad) + buzzer duration (b1 ).
Range 1 to 254 seconds
Global default 60 seconds