6.3.20 Motion sensor enable (Sn)
Display
Description Enables the input from the motion sensor.
Considerations Must be disabled if a motion sensor is not tted.
Range 0 (disabled) or 1 (enabled)
Global default 1 (enabled)
6.3.21 Display stability (d2)
Display
Description
Denes the rate of change of the displayed temperature.
Limiting the rate of change provides a dampening eect so as not to concern users
should the air temperature rise quickly due to a door opening.
Increasing the value for the display stability (d2) slows the rate of change of the
displayed temperature.
Considerations Use the global default value for normal operation.
Range 1 to 254
Global default 46
6.3.22 Low voltage (LO)
Display
Description
Denes the minimum voltage allowed before switching o the compressor. The low
voltage (LO) values are 10% of the actual line in voltages (see table below).
Considerations
• Must not be used with an external voltage stabiliser
• Must only be used with an Elstat supplied transformer
Global default 0 (disabled)