Menu 5.15.2 [S] Com. errors
Shows the total number of incorrect communications with
AMS 10 since start-up.
Menu 5.15.3 [S] Reset com. errors
Select "Yes" here to reset the counters in menu 5.15.1 and
5.15.2. The settings returns to ”No” once the action has
been carried out.
Setting range: Yes, No
Menu 5.15.4 [S] Return
Return to menu 5.15.0.
Menu 5.16 [N] Return
Return to menu 5.0.
6.0 [N] Room temperature*
Menu 6.1 [U] Room compensation
A factor is selected here that determines how much the
flow temperature is affected by the difference between
the room temperature and the set room temperature. A
higher value gives a greater change.
Setting range: 0 10.0
Default value: 2.0
Menu 6.2 [U] Heating system
Select here whether the room sensor should activate cli-
mate system 1 (menu 2.0) and/or climate system 2 (menu
3.0).
Setting range: Off, System 1, System 2, System 1+2
Default value: Off
Menu 6.3 [N] Room temp. setpoint
The desired room temperature is shown here.
Setting range: 10 30 °C
Menu 6.4 [U] Room temp avg. 1min
Shows the average room temperature over the last minute.
Menu 6.5 [U] Room integrator time
Select the integration time for room control here.
Setting range: 0 120
Factory setting: 0
Menu 6.6 [N] Return
Return to menu 6.0.
7.0 [N] Clock
Menu 7.1 [N] Date
The current date is set here.
Menu 7.2 [N] Time
Here the current time is set.
Menu 7.3.0 [U] Temp set back
Settings, e.g. for night reduction can be selected in the
sub-menus to this menu.
Menu 7.3.1 [U] Set back time
The time for the day change, e.g. night reduction is chosen
here.
Menu 7.3.2 [U] Set back temp +/-
Changes to the heat curve with a day change, e.g. the
night reduction is set here.
Setting range: -10 10
Factory setting: 0
Menu 7.3.3 [U] Heating system
The climate system that the day change is to affect is selec-
ted here. If shunt group 2 is present the menu can be set
to “Off”, “System 1”, “System 2” or “System 1+2”. In other
cases only "Off" and "System 1" can be selected.
Setting range: Off, System 1, System 2, System 1+2
Default value: Off
Menu 7.3.4 [U] Return
Return to menu 7.3.0.
Menu 7.4.0 [U] Extra hot water
Settings are made in the sub-menus of this menu when
extra hot water is required on a specific day.
Menu 7.4.1 7.4.7 [U] XHW Monday XHW Sunday
Here you select the period for respective days when extra
hot water should be activated. Hours and minutes for both
start and stop are shown. Equal values mean that extra
hot water is not activated. Time can be set past midnight.
Setting range: 00:00 23:45
Factory setting: 00:00 00:00
Menu 7.4.8 [U] Return
Return to menu 7.4.0.
Menu 7.5.0 [U] Vacation set back
Holiday settings are made in the sub-menus to this menu.
When the holiday function is active, the flow line temper-
ature is reduced according to the setting and hot water
charging can be switched off.
When the holiday function is deactivated, the heat pump
heats the water for an hour, before periodic extra hot
water is activated (if periodic extra hot water is activated
in menu 1.7).
NOTE
The holiday setting does not deactivate cooling.
Menu 7.5.1 [U] Vacation begins
The start date for holiday change is set here. The date is
changed by pressing the enter button. The holiday change
starts to apply at 00:00 on the selected date.
Same date in menu 7.5.1 and 7.5.2 deactivates the holiday
function.
*Requires accessory and activation in menu 9.3.6.
53NIBE™ SPLIT ACVM 270
Miscellaneous
Control

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nibe ACVM 270 and is the answer not in the manual?

Nibe ACVM 270 Specifications

General IconGeneral
BrandNibe
ModelACVM 270
CategoryAir Conditioner
LanguageEnglish

Related product manuals