Pipe connections
FIGHTER 200P
For the Installer
10
Pipe installation must be carried out in accordance with
current norms and directives.
The system requires a low-temperature dimensioning of
the radiator circuit. At DUT, the highest recommended
temperatures are 55 °C on the flow line and 45 °C on
the return line.
When the circulation pump is running, the flow in the
radiator circuit must not be completely stopped.
The total volume is 240 litres, with 170 litres in the water
heater and 70 litres in the boiler section.
The pressure vessel in the FIGHTER 200P is approved
for max 9.0 bar (0.9 MPa) in the water heater and
2.5 bar (0.25 MPa) in the double shell section.
Overflow water from the evaporator collection tray and
safety valves goes via non-pressurised collecting pipes
to a drain so that hot water splashes cannot cause
injury. These non-pressurised collecting pipes shall not
be used for anything else. A discharge pipe from the
tundish (108) connected to the expansion reliet valve
(47) (safety valve) shall also be connected to a drain in
the same way.
No valve should be fitted between the pressure reduc-
tion valve (expansion valve) and the storage cylinder.
General
500 mm maximum
300 mm
minimum
Tundish
Metal discharge pipe from
temperature relief value to tundish.
Metal discharge pipe from tundish,
with continous fall.
Discharge below
fixed grating.
Fixed grating
Trapped gulley
Possible wall
Safety device
(e.g. temperature
relief valve).
<G3> / 4 22 mm 28 mm up to 9 m 1,0 m
G1 / 2 15 mm 35 mm up to 27 m 1,4 m
<G3> / 4 22 mm 42 mm up to 27 m 1,7 m
<G3> / 4 22 mm 35 mm up to 18 m 1,4 m
G1 28 mm 42 mm up to 18 m 1,7 m
G1 28 mm 35 mm up to 9 m 1,4 m
Valve Minimum size of Minimum size of discharge Maximum resistance allowed, Resistance created
outlet size discharge pipe pipe from tundish expressed as a lenght by each elbow
of straight pipe or bend
(i.e. no elbows or bends)
G1 28 mm 54 mm up to 27 m 2,3 m
G1 / 2 15 mm 28 mm up to 18 m 1,0 m
G1 / 2 15 mm 22 mm up to 9 m 0,8 m
Table sizing of copper discharge pipe for common temperature relief valve outlet sizes.
Warning to the
installer!
Do not use collection funnel (99) to
discharge pipes from tundish (108).