2 Assembly and installation
BU 0600 en-2319 33
2.3.2 Output choke SK CO1
To reduce interference signals from the
motor cable or to compensate for cable
capacitance in long motor cables, an
additional output choke (motor choke)
can be installed into the inverter output.
During installation take care that the
pulse frequency of the frequency inverter
is set to 3 … 6 kHz (P504 = 3 … 6).
These chokes are specified for a
maximum supply voltage of 480 V at
0 … 100 Hz.
An output choke should be fitted for cable lengths over 100 m/30 m (unshielded/shielded). All chokes
have a protection class corresponding to IP00.
The choke used must therefore be installed in a
control cabinet.
Inverter ID
SK 5xxP
Output choke 3 x 200 ... 240 V
L1 B1 D
Detail: Fastening
Weight
Type
Continuous
current [A]
Inductance
[mH]
L2 B2
0.5 …0.75 kW
Material No.:
276996004
4 3 x 3.5
120
104 140 84 75 M6 4 2.8
1.1 ... 1.5 kW
Material No.:
276996009
9 3 x 2.5
155
110 160 130 71.5 M6 4 5.0
2.2 kW
Material No.:
276996017
17 3 x 1.2
185
102 201 170 57.5 M6 10 8.0
[mm] [mm
]
[kg]
Table 11: Output choke data for SK CO1-..., 3~ 240 V