5.1.4 Control parameters
P300 Control method P
Factory setting { 0 }
The control method for the motor is defined with this parameter. The following
constraints must be observed: In comparison with setting "0", setting "2" enables
higher dynamics and control precision, however it requires greater effort for
parameterisation. Setting "1" operates with speed feedback from an encoder and
therefore enables the highest possible quality of speed control and dynamics.
Commissioning information: ( Section 4.2 "Selecting the operating mode for motor
control").
Setting values
Value Meaning
0 VFC open-loop Speed control without encoder feedback
1 CFC closed-loop Speed control with encoder feedback
Speed control without encoder feedback
P301 Encoder resolution
Setting range 0 … 27
Factory setting { 6 } { 3 } { 5 }
"Encoder resolution". Input of the pulse-count per rotation of the connected encoder.
If the direction of rotation of the encoder is not the same as the FI, (depending on
installation and wiring), this can be compensated by selecting the corresponding
negative pulse numbers.
P301 is also significant for position control via incremental encoders. If an incremental
encoder is used for positioning (P604=1), the setting of the pulse number is made
here (see supplementary POSICON manual).
Value Value
0 500 pulses 8 -500 pulses
2 1000 pulses 10 -1000 pulses
3 1024 pulses 11 -1024 pulses
4 2000 pulses 12 -2000 pulses
6 4096 pulses 14 -4096 pulses
7 5000 pulses 15 -5000 pulses
16 -8192 pulses
18 16 pulses 23 -16 pulses
19 32 pulses 24 -32 pulses
20 64 pulses 25 -64 pulses
22 256 pulses 27 -256 pulses